A flammable liquid storage room is the most heavily prescribed special hazard in this category, because NFPA 30 does not leave much to interpretation. The liquid class determines the maximum allowable quantity permitted in a control area, the quantity and configuration determine the required room construction and fire resistance rating, and both together determine the suppression density and whether foam is required. Get the classification wrong and everything downstream of it is wrong.
The distinctive feature of the hazard is that the fuel is mobile. A drum failure, a container breach, or a fire that softens plastic containers releases liquid that flows, spreads across the floor, and travels through any opening it finds, including door undercuts, floor drains, and conduit penetrations. This is why NFPA 30 requires spill control and secondary containment as a core provision rather than an enhancement: keeping the liquid in the room is as important as putting the fire out.
Water is also a complication rather than a straightforward solution. A water spray applied to burning flammable liquid can carry unburned fuel with it and extend the fire footprint, and the water added during suppression increases the total liquid volume the containment has to hold. This is why protection on these rooms normally combines foam or foam-water suppression with containment sized for both the stored liquid and the suppression water, and why a room protected by ordinary sprinklers with an undersized curb is a worse configuration than it appears.